About the Beckhoff EL6900
The Beckhoff EL6900 is an EtherCAT Terminal providing a TwinSAFE Logic safety controller for Boolean safety functions, acting as a link unit between safe input and output signals. It supports up to 128 safe connections via FSoE and is programmed with TwinCAT 3 Safety Editor or TwinCAT 2. The compact 12 mm wide housing mounts on 35 mm DIN rail, is rated IP20, and is certified to DIN EN ISO 13849-1 Cat. 4 PL e and EN 61508 SIL 3.
Beckhoff EL6900 is a safety controller terminal available from EP4 Solutions in new, unused condition. It is also referenced by the part number 070935.
This item is available to order. Contact our team for the current lead time. Priced at £144.26 excluding VAT.
Suited to machine safety architectures that need Boolean safety logic linking safe inputs and outputs over EtherCAT. Hazardous area use is covered by the listed ATEX, IECEx and cFMus markings (Zone 2 / Division 2 ratings), subject to the specification for your site.
EP4 Solutions is an industrial distributor, supplying electrical, controls and automation parts to industry since 1994. Trade accounts, quotations and worldwide delivery are available.
Brand new, unused product.
Specification sources: beckhoff.com
Specifications
| Manufacturer | Beckhoff |
|---|---|
| Part number | EL6900 |
| Alternative part numbers | 070935 |
| Product type | Safety Controller Terminal |
| Condition | New |
| Availability | Available to order |
| Price (ex VAT) | £144.26 |
| Current consumption E-bus | typ. 188 mA |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
| Weight | approx. 50 g |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Protection rating | IP20 |
| Safety standard | DIN EN ISO 13849-1:2008 (Cat. 4, PL e) and EN 61508:2010 (SIL 3) |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc; IECEx: Ex ec IIC T4 Gc; cFMus: Class I, Division 2, Groups A, B, C, D; Class I, Zone 2, AEx ec IIC T4 Gc |
| Specification | link unit between safe input and output signals |
| Protocol | TwinSAFE/Safety over EtherCAT |
| Current load power contacts | Imax: 10 A |
| Current consumption power contacts | – |
| Cycle time | approx. 500 µs/according to project size |
| Fault response time | ≤ watchdog time (parameterizable) |
| Material | polycarbonate |
| Design form | compact terminal housing with signal LEDs |
| Housing type | EL-12-8pin |
| Installation position | horizontal |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
| Stripping length | 8…9 mm |
| RoHS | compliant with exemption (7c-I) |
| REACH SVHC | no |