About the Schneider Electric GV2P06
The Schneider Electric GV2P06 is a new three-pole motor circuit breaker from the TeSys Deca frame 2 (TeSys GV2) range, with thermal-magnetic protection and a 1 to 1.6 A thermal adjustment range. It is rated up to 690 V AC with a breaking capacity of 100 kA Icu at 400/415 V AC, and uses screw clamp terminals with a rotary handle operator. It mounts on a 35 mm DIN rail or by panel screwing (2 x M4) and has an IP20 degree of protection and an operating ambient temperature of -20 to 60 °C.
Schneider Electric GV2P06 is a motor circuit breaker available from EP4 Solutions in new, unused condition. It is also referenced by the part number 3781141.
This item is available to order. Contact our team for the current lead time. Priced at £40.20 excluding VAT.
Suited to motor protection in AC control panels, where a 0.37 kW or 0.55 kW motor at 400/415 V AC, or 0.75 kW at 690 V AC, is to be protected. Listed by the manufacturer for UKCA and several other certification schemes.
EP4 Solutions is an industrial distributor, supplying electrical, controls and automation parts to industry since 1994. Trade accounts, quotations and worldwide delivery are available.
Brand new, unused product.
Specification sources: se.com
Specifications
| Manufacturer | Schneider Electric |
|---|---|
| Part number | GV2P06 |
| Alternative part numbers | 3781141 |
| Product type | Motor Circuit Breaker |
| Condition | New |
| Availability | Available to order |
| Price (ex VAT) | £40.20 |
| [In] rated current | 1.6 A |
| Thermal protection adjustment range | 1…1.6 A conforming to IEC 60947-4-1 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 (also listed at 230/240, 440, 500 and 690 V AC) |
| Motor power kW | 0.37 kW at 400/415 V AC 50/60 Hz; 0.55 kW at 400/415 V AC 50/60 Hz; 0.37 kW at 500 V AC 50/60 Hz; 0.55 kW at 500 V AC 50/60 Hz; 0.75 kW at 690 V AC 50/60 Hz |
| Connection - terminals | Screw clamp terminals |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C |
| Product name | TeSys Deca |
| Device short name | GV2P |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Poles description | 3P |
| Network type | AC |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Magnetic tripping current | 22.5 A |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 1.6 A conforming to IEC 60947-4-1 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240, 400/415, 440, 500 and 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Power dissipation per pole | 2.5 W |
| Suitability for isolation | Yes conforming to IEC 60947-1 § 7-1-6 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Tightening torque | 1.7 N.m on screw clamp terminals |
| Control type | Rotary handle |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 2 x M4 screws) |
| Height | 89 mm |
| Width | 45 mm |
| Depth | 97 mm |
| Colour | Dark grey |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Package 1 Weight (packaging, 1 unit) | 320 g |
| IK degree of protection | IK04 |
| Ambient air temperature for storage | -40…80 °C |
| Operating altitude | 2000 m |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Climatic withstand | Conforming to IACS E10 |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1 |
| Product certifications | CCC; UL; CSA; EAC; ATEX; LROS; BV; RINA; DNV-GL; UKCA |
| Warranty | 18 months |