KFD2-GUT-Ex1.D
Also known as: 231225, KFD2 GUT EX1 D
- Brand new, unused
- Worldwide delivery & export docs
- Trade accounts available
- Call 0151 346 1380 for urgent requirements
About the Pepperl+Fuchs KFD2-GUT-Ex1.D
The Pepperl+Fuchs KFD2-GUT-Ex1.D is a new 1-channel isolated barrier temperature converter from the K-System series, for intrinsic safety applications. It accepts thermocouple, RTD, potentiometer or voltage input and provides a 0/4 mA to 20 mA current output plus two relay contact outputs. Supply is 20 to 30 V DC, via terminals or a Power Rail, with an ambient range of -20 to 60 °C and up to SIL 2 acc. to IEC/EN 61508 and IEC/EN 61511. Configuration is via PACTware or the keypad.
Pepperl+Fuchs KFD2-GUT-Ex1.D is a temperature converter available from EP4 Solutions in new, unused condition. It is also referenced by the part numbers 231225, KFD2 GUT EX1 D.
This item is available to order. Contact our team for the current lead time. Priced at £545.45 excluding VAT.
Suited to measuring temperature in hazardous areas where an intrinsically safe signal path to the control system is required, with the output feeding a current loop input. The SIL 2 rating also supports safety-related temperature monitoring applications.
EP4 Solutions is an industrial distributor, supplying electrical, controls and automation parts to industry since 1994. Trade accounts, quotations and worldwide delivery are available.
Brand new, unused product.
Specification sources: pepperl-fuchs.com
Specifications
| Manufacturer | Pepperl+Fuchs |
|---|---|
| Part number | KFD2-GUT-Ex1.D |
| Alternative part numbers | 231225, KFD2 GUT EX1 D |
| Product type | Temperature Converter |
| Condition | New |
| Availability | Available to order |
| Price (ex VAT) | £545.45 |
| Safety Integrity Level (SIL) | SIL 2 |
| Rated voltage (Ur) | 20 ... 30 V DC |
| Output III current range | 0 ... 20 mA or 4 ... 20 mA |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 |
| Mass | 300 g |
| Dimensions (W x H x D) | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) |
| Signal type | Analog input |
| Connection | terminals 23+, 24- or power feed module/Power Rail |
| Rated current (Ir) | approx. 100 mA |
| Power dissipation/power consumption | ≤ 2 W / 2.2 W |
| Programming interface | programming socket |
| Connection (field side) | terminals 1, 2, 3, 4, 6 |
| RTD types | Pt100, Pt500, Pt1000, Ni100, Ni1000 |
| Lead resistance | max. 50 Ω |
| Thermocouple types | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) |
| Potentiometer | 0.8 ... 20 kΩ |
| Voltage input | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV |
| Input resistance | ≥ 250 kΩ (0 ... 10 V); min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) |
| Measuring current | approx. 400 µA with resistance measuring sensor |
| Output I, II | relay |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A V AC / A |
| Mechanical life | 5 x 10^7 switching cycles |
| Energised/de-energised delay | approx. 20 ms / approx. 20 ms |
| Open loop voltage | max. 24 V DC |
| Load | max. 650 Ω |
| Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
| Sampling rate | approx. 700 ms |
| Rated insulation voltage | 300 Veff (reinforced insulation acc. to IEC/EN 61010-1) |
| Connection | screw terminals |
| Housing type | C2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | TÜV 03 ATEX 2140 |
| Marking | Ex-Hexagon II (1)G [Ex ia Ga] IIC; II (1)D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
| Maximum safe voltage (supply) | Um 40 V DC |
| Input terminals 2, 6 (active equipment) | Uo 13.1 V; Io 8 mA; Po 67 mW; Ui 29 V; Ii 11 mA; Pi 200 mW |
| Inputs terminals 1, 2, 3, 4, 6 (passive equipment) | Uo 13.1 V; Io 21 mA; Po 67 mW |
| Certificate (Ex nA/nC) | PF 08 CERT 1213 X; marking Ex-Hexagon II 3G Ex nA nC IIC T4 Gc |
| Galvanic isolation (Ex ia) | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| IECEx certificate | IECEx TUN 09.0019 |
| Electromagnetic compatibility | Directive 2014/30/EU; EN 61326-1:2013 (industrial locations) |
| Low voltage | Directive 2014/35/EU; EN 61010-1:2010 |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020; EN IEC 60079-11:2024; EN 60079-15:2010 |
Our sourcing team finds obsolete and discontinued parts every day.