NewKFU8-SR-Ex1.W
Also known as: 204137, KFU8SREX1W
- Brand new, unused
- Worldwide delivery & export docs
- Trade accounts available
- Call 0151 346 1380 for urgent requirements
About the Pepperl+Fuchs KFU8-SR-Ex1.W
The Pepperl+Fuchs KFU8-SR-Ex1.W is a new single-channel isolated switch amplifier for intrinsic safety applications. It takes NAMUR sensor or dry contact inputs and provides a relay contact output with line fault detection. It is rated up to SIL 2 (SC 3) to IEC/EN 61508, supplied from 19 ... 30 V DC or 90 ... 253 V AC (50 ... 60 Hz), and mounts on a 35 mm DIN rail.
Pepperl+Fuchs KFU8-SR-Ex1.W is a switch amplifier available from EP4 Solutions in new, unused condition. It is also referenced by the part numbers 204137, KFU8SREX1W.
This item is available to order. Contact our team for the current lead time. Pricing is on request: add it to your quote list for a fast, competitive response.
Suitable for intrinsically safe switching of NAMUR sensors or dry contacts in hazardous areas, where line fault detection and a relay output are required. Certified to ATEX, IECEx and UL (cULus) for the relevant installations.
EP4 Solutions is an industrial distributor, supplying electrical, controls and automation parts to industry since 1994. Trade accounts, quotations and worldwide delivery are available.
Brand new, unused product.
Specification sources: pepperl-fuchs.com
Specifications
| Manufacturer | Pepperl+Fuchs |
|---|---|
| Part number | KFU8-SR-Ex1.W |
| Alternative part numbers | 204137, KFU8SREX1W |
| Product type | Switch Amplifier |
| Condition | New |
| Availability | Available to order |
| Price | On request |
| Safety Integrity Level (SIL) | SIL 2 |
| Rated voltage Ur | 19 ... 30 V DC / 90 ... 253 V AC 50 ... 60 Hz |
| Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load V / A |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F); extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
| Degree of protection | IP20 |
| Mass | approx. 150 g kg |
| Dimensions (W x H x D) | 20 x 119 x 115 mm, housing type B2 |
| Signal type | Digital Input |
| Systematic capability (SC) | SC 3 |
| Power dissipation/power consumption | ≤ 1 W / ≤ 1 W ; 3 VA |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA V DC / mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
| Output | signal ; relay |
| Minimum switch current | 2 mA / 24 V DC |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Mechanical life | 107 switching cycles |
| Switching frequency | < 10 Hz |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
| Connection | screw terminals |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Input (Ex) | Ex ia |
| Voltage Uo | 10.5 V |
| Current Io | 13 mA |
| Power Po | 34 mW (linear characteristic) |
| Marking | II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc; II (1)D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
| Maximum safe voltage Um (supply and output) | 253 V AC |
| Safe electrical isolation (input/output and input/power supply) | acc. to IEC/EN 60079-11, voltage peak value 375 V |
| UL approval | E106378 |
| Control drawing | 116-0489 |
| IECEx certificate | IECEx FIDI 22.0003X |
| EU-type examination certificate | FIDI 22 ATEX 0029 X |
| EMC directive | Directive 2014/30/EU; EN 61326-1:2013 (industrial locations) |
| Low voltage directive | Directive 2014/35/EU; EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
| Explosion protection directive | Directive 2014/34/EU; EN IEC 60079-0:2018, EN 60079-7:2015+A1:2018, EN 60079-11:2012, EN IEC 60079-15:2019 |
| Standard | IEC 60529:1989+A1:1999+A2:2013 |